DCPS
Specification- Single Unit |
Model |
PSD-12 |
PSD-12 |
PSD-12 |
Output |
DC VOLTAGE |
12V |
24 V |
48 V |
RATED CURRENT |
(5 to 15 A ) |
( 2 to 6 ) |
( 5A) |
RATED POWER |
720W |
960W |
1008 W |
RIPPLE & NOISE (max) Note 2 |
150mVp-p |
200mVp-p |
300 m Vp-p |
VOLTAGE ADj. RANGE |
11.6 ~12.4 V |
23.2 ~ 24.8 V |
46.3 ~ 49.7 V |
VOLTAGE TOLERANCE Note 3 |
+ 1.0% |
+ 1.0% |
+ 1.0% |
LINE REGULATION |
+ 0.5% |
+ 0.5% |
+ 0.5% |
LOAD REGULATION |
+ 0.5% |
+ 0.5% |
+ 0.5% |
SETUP,RISE TIME |
1000 ms, 60ms/230 VAC at full load |
HOLD UP TIME (Typ) |
16 ms/230 VAC at full load |
Input |
VOLTAGE RANGE Note 5 |
90 ~264 VAC 127 ~370 VDC |
FREQUENCY RANGE |
47 ~ 63 Hz |
EFFICIENCY (Typ) |
81% |
87% |
89% |
AC CURRENT (Typ.) |
8.5A/115 VAC 10.5A/115 V AC |
10.5A/115 VAC 5.5A/230 VAC |
11A/115 VAC 5.5A/230 VAC |
INRUSH CURRENT (Typ.) |
COLD START 50A |
LEAKAGE CURRENT |
1.1mA / 230 VAC |
Protection |
OVERLOAD |
105 ~ 125% rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed |
OVER TEMPERATURE
|
75 ˚C+ 5˚C ( TSW1) 85˚C+5˚C ( TSW2)
detect on heat sink of power transistor detect on heat sink of power diode |
Protection type : Shutdown o/p voltage, recovers automatically after temperature goes down |
OVER VOLTAGE
|
13.2 ~ 16.2V 26.4 ~ 32.4V 52.8 ~ 64.8V
|
Protection type : Shutdown o/p voltage, re-power on to recover |
|